Calectro - UG-3-A5-0

Manufacturer Calectro
Part Number UG-3-A5-0
Inner Code 3429413
Description air duct smoke switch
Custom Code 85311030
Technical specification 230 V AC The Uniguard smoke detector was developed and combined to detect smoke in ventilation ducts a smoke detector with an adapter system, with tube and casing specifically designed for optimal airflow were designed by the smoke detector. The Unifuard smoke detector has an integrated Alarm relay for controlling ventilation flaps, stopping fans and activating acoustic and optical alarms, etc. The integrated service alarm relay informs you about upcoming maintenance before false alarms occur. The smoke detector has an intelligent control and monitoring circuit. This circuit adjusts sensitivity for optimal to allow the smoke detector to function over its entire service life. If the monitoring circuit can no longer compensate for contamination, a service alarm will occur issued. Uniguard Superflow has four pre-assembled cable entries with IP67 approval with automatic pull load anchoring for cable diameters of 4-11 mm, type Klikseal. The bayonet mount of the smoke detector makes it easier to install and remove. TECHNICAL DATA Power supply: 230 V AC ± 20% Max Power Consumption: 18mA Operating temperature ፦10°C to +55°C Maximum humidity: 99% RH Channel ventilation performance range: approx. 0.2 to 20 m/s approvals UG-3-A5O: VdS (Germany) detecter head: EN-54-7 Relay output: floating Smoke alarm relay: two 250 V, 5 A switching contacts Service alarm: one switching contact 250 V, 5 A Degree of protection: IP54
Weight 1.3

Please contact us to request a price quote for Calectro - UG-3-A5-0, or for any other model as well. We offer competitive prices, fast delivery and a wide products distribution network in the UK.


WE SELL ONLY NEW AND ORIGINAL PRODUCTS!

Our company is not an authorized distributor. All rights are reserved by the manufacturers and their official partners.

Calectro-UG-3-A5-0 price

More products of Calectro

Other Category Brands